When a wire melts

A cable carrying far more current than it's rated for heats up, eventually hot enough that the insulation softens and then breaks down. How fast that happens depends on three things only: cross-section, current, and insulation material.

Where the heat comes from

Every current-carrying conductor has electrical resistance, and power dissipates as heat across it:

P=I2⋅RP = I^2 \cdot R

Double the current and the power dissipated quadruples, which is why a short circuit heats up so much faster than an ordinary overload. Resistance itself isn't constant either, it rises with temperature:

R(θ)=ρ20⋅(1+α⋅(θ−20))SR(\theta) = \frac{\rho_{20} \cdot (1 + \alpha \cdot (\theta - 20))}{S}

ho20 ho_{20} is copper's resistivity at 20 °C, α≈0.00393 /extK\alpha \approx 0.00393\,/ ext{K} its temperature coefficient, SS the cross-section. At the same current, a hot cable heats up slightly faster than a cold one: a small, self-reinforcing effect.

The same formula, rearranged

Cable short-circuit withstand follows the adiabatic approximation used in DIN VDE 0100-430 / IEC 60364-4-43. Adiabatic here means: over that short a time, essentially no heat escapes to the surroundings, it all stays in the conductor.

t=(k⋅SI)2t = \left( \frac{k \cdot S}{I} \right)^2

The material constant kk is itself just a compact way of writing the temperature rise from a starting temperature hetai heta_i to a limit temperature hetaf heta_f:

k(θf)=226⋅ln⁡θf+234θi+234k(\theta_f) = 226 \cdot \sqrt{\ln \frac{\theta_f + 234}{\theta_i + 234}}

234 is a material constant for copper, the reciprocal of its temperature coefficient. 226 bundles up copper's density, specific heat and resistivity at 20 °C. Plug in hetai=70 °extC heta_i = 70\,° ext{C} (its rated continuous temperature) and hetaf=160 °extC heta_f = 160\,° ext{C} (the short-circuit limit) for PVC insulation, and out comes k≈115k \approx 115, the same figure already published as a table value in the short-circuit simulator on the blog. It's the same formula, just solved for kk instead of tt.

Solve t=(k(θf)⋅S/I)2t = (k(\theta_f) \cdot S / I)^2 for hetaf heta_f instead, and instead of a single withstand time you get the whole temperature as a function of time:

θ(t)=(θi+234)⋅exp⁡ ⁣((It226⋅S) ⁣2)−234\theta(t) = (\theta_i + 234) \cdot \exp\!\left( \left( \frac{I \sqrt{t}}{226 \cdot S} \right)^{\!2} \right) - 234

That's the curve the calculator below plots.

The calculator

Power dissipation
–
Starts to soften
–
Fully melted away
–
Melting duration
–

Adiabatic (no heat escapes to the surroundings), valid for a genuine overload/short-circuit event, not for continuous operation near the rated load, see the text below. θonset = 160°C / k≈115 for PVC is the short-circuit limit temperature from DIN VDE 0100-430 (the same figure used in the short-circuit simulator above, in the blog). θfull is not a standard value, it is a rough assumption of this tool’s own for "nothing recognizable as insulation is left", real PVC has no sharp melting point like ice: it softens, bubbles and decomposes over a range.

Pick a cross-section and insulation, then drag the slider: the curve shows the conductor temperature climbing over time, with two markers for where the insulation starts to soften and where this model treats it as fully decomposed.

At low overload factors, the temperature stays under the softening threshold within the displayed window, and the calculator deliberately shows no result. Something is still happening there, just slower than the underlying assumption allows for: no heat escaping to the surroundings stops holding once an overload runs for a minute or more. In reality, the cable sheds some of that heat through the insulation, the air and its surroundings, and settles at a lower, stable temperature instead of heating up forever.

What about cable length?

A longer cable should handle a short circuit better, the thinking goes: more copper to soak up the heat, more surface to shed it. It doesn't. t=(k(θf)⋅S/I)2t = (k(\theta_f) \cdot S / I)^2 has no length term at all, on purpose.

Every metre of cable carries the same current, has the same cross-section, and starts at the same temperature, so every metre heats up identically and in parallel. What happens to the metre 10 cm from the fault has no bearing on what happens 10 m away, because heat generated inside the conductor escapes radially into the insulation and surrounding air, not sideways along the copper to some cooler stretch of cable. A 1 m run and a 100 m run of the same cross-section reach the exact same temperature under the exact same overload.

Even if heat could travel along the cable, a short circuit doesn't last long enough for it to matter: copper's thermal diffusivity puts the distance heat can conduct axially in a second or two at roughly 1–2 cm, nowhere near enough to reach a cooler part of the run before the fault clears (or the insulation is already gone). That's the same reason the adiabatic assumption behind this whole calculation holds in the first place.

The same logic applies to the ampacity table further down: it's a per-metre rating too, which is why it doesn't have a length column either. Cable length matters for other things on a real installation, voltage drop and total power loss chief among them, just not for the temperature this calculator works out.

What "fully melted away" isn't

The 160 °C onset-of-softening figure is straight from the standard. The 300 °C for "fully melted away" isn't, it's a rough call of this tool's own for the point where nothing recognizable as insulation is left. PVC has no sharp melting point like an ice cube. It softens, deforms, and starts breaking down chemically, releasing hydrogen chloride among other things, long before anything melts in the sense of turning liquid. The second figure in the calculator is best read as an order of magnitude, not an exact measurement.

Why this doesn't happen in practice

This calculation describes what would happen to the cable on its own. It's exactly why circuit breakers exist: a properly sized B, C or D breaker trips on a real short circuit long before the cable behind it feels anything from this curve. The short-circuit simulator in the other post pits breaker and cable against each other directly. Here it's just the cable by itself, without the protection that actually covers it in real operation.

How this compares to the standard table

The calculation above answers a different question than the table most electricians actually plan from: a cable's continuous current rating (ampacity, IzI_z) in normal operation, with real cooling through the wall, conduit or air, depending on how it's installed.

Cross-sectionInsulated wallConduit / trunkingCable tray / under ceiling
1.5 mm²14 A / 13 A16 A / 16 A18.5 A / 16 A
2.5 mm²18.5 A / 16 A21 A / 20 A25 A / 25 A
4 mm²24 A / 20 A29 A / 25 A34 A / 32 A
6 mm²31 A / 25 A36 A / 35 A43 A / 40 A
10 mm²41 A / 40 A49 A / 40 A60 A / 50 A
16 mm²55 A / 50 A66 A / 63 A81 A / 80 A
25 mm²72 A / 63 A85 A / 80 A102 A / 100 A
35 mm²88 A / 80 A105 A / 100 A126 A / 125 A
50 mm²105 A / 100 A125 A / 125 A153 A / 125 A
70 mm²133 A / 125 A158 A / 125 A195 A / 160 A
95 mm²159 A / 125 A190 A / 160 A236 A / 224 A
120 mm²182 A / 160 A218 A / 200 A275 A / 250 A

Each cell: ampacity / usual breaker or fuse rating.

Copper conductor, 25 °C ambient, a single core installed in a heat-insulated wall, in conduit or trunking, or on cable tray/under the ceiling, each paired with the breaker or fuse rating usually chosen for it.

That's the same principle behind every circuit breaker: the protective device's rated current InI_n sits at or below the cable's ampacity IzI_z, so the breaker trips before the cable overheats for good, not after.

The calculator above deliberately models the case where that no longer holds: a fault current far above these table values, briefly, with no heat escaping to the surroundings. Take a 2.5 mm² PVC cable in conduit: the table allows 21 A continuous, protected by a 20 A breaker. Push 500 A through it instead, say during a solid short circuit, and the calculator above shows softening well under a second later.

For aluminium conductors, go at least one cross-section size up from the copper equivalent, and above 70 mm² closer to two sizes because of the larger voltage drop. All figures without guarantee, real installation conditions (bundling, ambient temperature, insulation) can differ and need checking case by case.

Simplified physical model for illustration, not a basis for real cable sizing. The adiabatic approximation only holds for short, severe overloads; the decomposition temperature is a rough assumption of this tool's own, not a standard value. Selection, protection and sizing of a real installation belong in the hands of a qualified electrician.